3KF3325-0LF11
SW.DISCON. W.F. 3-P 250A/SZ.1

From SIEMENS

Switch disconnector with fuse 250 A, Size 3, 3-pole for LV HRC fuse Sz. 0 and 1 Front operating mechanism left Basic unit without handle flat terminal
Model
Product brand nameSENTRON
Product designationSwitching device
Design of the product3KF switch disconnector with fuses
Design of the operating mechanismwithout
Design of handleWithout
Direction of actuationfrom the front
Type of the driving mechanism / motor driveNo
Number of poles3
Size of disconnecting link1 and 0
Size of switch disconnector3
Size of fuse linkNH0, NH1
Electrical endurance (switching cycles)
at AC-23 A / at 440 V / at 50/60 Hz5 000
at AC-23 A / at 690 V / at 50/60 Hz4 000
at DC-23 A / at 440 V1 000
I2t value
with closed switch / for combination switch + fuse / at 500 V / maximum437 000 A²·s
with closed switch / for combination switch + fuse / at 400 V / maximum437 000 A²·s
with closed switch / at 690 V / for combination switch + gG fuse / maximum490 100 A²·s
of the fuse / at 500 V / maximum permissible1 500 000 A²·s
of the gG fuse / at 690 V / maximum permissible940 000 A²·s
of the aM fuse / at 690 V / maximum permissible1 400 000 A²·s
Mechanical service life (switching cycles) / typical10 000
Position / of the switch operating mechanismat the left end
Fuse systemLV HRC fuse
Overvoltage categoryIV
Operating voltage / with current paths in series
with degree of pollution 2 / at DC / rated value / Note440 / 3
with degree of pollution 3 / at DC / rated value / Note440 / 3
Insulation voltage / rated value1 000 V
Surge voltage resistance / rated value12 kV
Overvoltage in percent / relative to the operating voltage / at AC / at 50/60 Hz10 %
Protection class
Protection class IPIP00
Protection class IP
with closed switch / with cover or cable lug coverIP20
on the frontIP00
Dissipation
Power loss [W]
with conventional rated thermal current / per pole15 W
with conventional rated thermal current / per device45 W
with conventional rated thermal current / without fuse / per pole15 W
with conventional rated thermal current / without fuse / per device45 W
for rated value of the current / at AC / in hot operating state / per pole15 W
of the fuse / per fuse / maximum25.5 W
Operating current
at AC-21 A / at 400 V / maximum250 A
at AC-21 A / at 500 V / maximum250 A
at AC-21 A / at 690 V / maximum250 A
at AC-23 A / at 500 V / at 50/60 Hz / rated value / maximum250 A
at AC-22 A / at 500 V / at 50/60 Hz / rated value / maximum250 A
at AC-22 A / at 400 V / at 50/60 Hz / rated value / maximum250 A
at AC-22 A / at 690 V / at 50/60 Hz / rated value / maximum250 A
at AC-23 A / at 400 V / at 50/60 Hz / rated value / maximum250 A
at AC-23 A / at 690 V / at 50/60 Hz / rated value / maximum250 A
at DC-23 A / at 440 V / rated value / maximum250 A
at DC-23 A / at 220 V / rated value / maximum250 A
at DC-22 A / at 440 V / rated value / maximum250 A
at DC-22 A / at 220 V / rated value / maximum250 A
at DC-21 A / at 440 V / rated value / maximum250 A
at DC-21 A / at 220 V / maximum250 A
Continuous current
rated value250 A
at 40 °C / rated value250 A
at 45 °C / rated value250 A
at 50 °C / rated value250 A
at 55 °C / rated value250 A
at 60 °C / rated value250 A
at 65 °C / rated value250 A
at 70 °C / rated value200 A
Continuous current / at DC / rated value250 A
Let-through current / of the fuse / at 500 V / maximum permissible33 700 A
Let-through current / of the gG fuse / at 690 V / maximum permissible37 700 A
Let-through current / of the aM fuse / at 690 V / maximum permissible39 700 A
Let-through current / with closed switch
at 690 V / for combination switch + aM fuse / maximum permissible30 310 A
at 690 V / for combination switch + gG fuse / maximum permissible30 310 A
for combination switch + fuse / at 400 V / maximum permissible28 700 A
for combination switch + fuse / at 500 V / maximum permissible28 700 A
Short-time current resistance (Icw) / at 690 V AC/440 V DC / limited to 1 s / rated value8 kA
Main circuit
Operating power / at AC-23 A
at 400 V / at 50/60 Hz / rated value132 kW
at 500 V / at 50/60 Hz / rated value160 kW
at 690 V / at 50/60 Hz / rated value250 kW
Operating voltage
at AC / at 50/60 Hz / rated value690 V
at AC / rated value / maximum690 V
Auxiliary circuit
Number of connected NC contacts / for auxiliary contacts0
Number of connected NO contacts / for auxiliary contacts0
Number of connected CO contacts / for auxiliary contacts0
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts8
Number of NO contacts / for auxiliary contacts8
Suitability for use
Main switchYes
switch disconnectorYes
EMERGENCY OFF switchYes
safety switchYes
maintenance/repair switchYes
Product feature / interlockNo
Product component
Phase failure monitoringNo
Voltage triggerNo
undervoltage releaseNo
undervoltage release with leading contactNo
Product feature / sealableYes
Product extension
Auxiliary switchYes
optional
— locking capabilityYes
— motor driveNo
— fuse monitoringYes
Product function
fuse monitoringNo
Overvoltage protection monitoringNo
Short circuit
Short-circuit current making capacity (Icm) / for switch disconnector / at 690 V AC/440 V DC / without fuse link / rated value / minimum13.6 kA
Connections
Arrangement of electrical connectors / for main current circuitTop and bottom
Tightening torque / with screw-type terminals
minimum30 N·m
maximum44 N·m
Type of connectable conductor cross-sections / for aluminum conductor / stranded / with lug1x (6 ... 240 mm²), 2x (6 ... 120 mm²)
Type of connectable conductor cross-sections / for copper conductor / stranded / with lug / acc. to DIN 462341x (6 ... 240 mm²), 2x (6 ... 120 mm²)
Type of connectable conductor cross-sections / for copper conductor / stranded / with lug / acc. to DIN 462351x (6 ... 240 mm²), 2x (6 ... 120 mm²)
Type of electrical connection
for main current circuitflat connector
Mechanical Design
Height207 mm
Width249.5 mm
Depth188.5 mm
Mounting positionany
Mounting typefloor mounting
Mounting type
front mounting with 4-hole attachmentNo
front mounting with central attachmentNo
rail mountingNo
Net weight4 250 g
Environmental conditions
Degree of pollution3
Ambient temperature
during operation / minimum-25 °C
during operation / maximum70 °C
during storage / minimum-50 °C
during storage / maximum80 °C

External links