BVP:903789 LDA5415-UL-Z*
From SIEMENS
LDA5415-UL-Z* U unit flat Z dimension up to 0.99 m X/Y 0.5 m | ||
Model | ||
Product designation | L unit (junction unit) for LD busbar trunking system | |
Protection class | ||
Protection class IP | IP54 | |
Main circuit | ||
Operating frequency / rated value | ||
minimum | 16.7 Hz | |
maximum | 60 Hz | |
Operating voltage / at AC | ||
at 50 Hz / rated value / maximum | 1 000 V | |
at 60 Hz / rated value / maximum | 1 000 V | |
Operating current | ||
for circuit 1 / at AC / at 50 Hz / for horizontal busbar box with flat busbars / rated value / maximum | 1 700 A | |
for circuit 1 / at AC / at 50 Hz / for vertical busbar box / rated value | 1 800 A | |
for circuit 1 / at AC / at 50 Hz / rated value / maximum | 1 800 A | |
for circuit 1 / at AC / at 60 Hz / for horizontal busbar box with flat busbars / rated value / maximum | 1 700 A | |
for circuit 1 / at AC / at 60 Hz / for vertical busbar box / rated value | 1 800 A | |
for circuit 1 / at AC / at 60 Hz / rated value / maximum | 1 800 A | |
Connections | ||
Conductor cross section / of the (PE)N | 706 mm² | |
Mechanical Design | ||
Height | 180 mm | |
Width | 990 mm | |
Mounting type | ceiling / wall | |
Material / of the busbar | aluminium |